Abstract

SummaryNine participants, representing eight different Swedish fire consultancy firms participated in a Round Robin study where two different cases were simulated with the Fire Dynamics Simulator. The first case included a large open warehouse where the activation of a sprinkler system was to be studied. In the second case time to critical conditions in a theatre was to be calculated. The participants were given clear instructions on the building layout and heat release rate for the two cases. Still, the results demonstrate a significant variation in time to sprinkler system activation (range of 110 seconds) and available safe escape time (range of 60 seconds), between the participants. It is important to emphasise that some degree of variation is unavoidable, as engineers can model things differently without the modelling solution necessarily being incorrect. Even though it is hard to isolate and specific cause of the variation, some of the variation seen in this study is related to modelling choices that are questionable and consequently problematic for the reliability of the fire safety design.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.