Abstract
In this paper an approach for on-line identification of parameters and dynamic states of synchronous generator, is proposed. Synchrophasors data and Hybrid Dynamic Simulation provide the trajectories deviations caused by parameters errors. Simulated variables are combined with measurements to obtain Hybrid Trajectory Sensibility Functions (HTSF), which are used in the identification process based on Nonlinear Least Squares. This approach simplifies the calculation of HTSF. Constraints on the parameters range are enforced and the resulting constrained optimization problems is solved by a Primal-Dual Interior Points method. This solution is discussed in the paper. The method is applied to synthetic data and to a large generator of the Itaipu power plant.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.