Abstract

The doubly-fed induction generator has significant features compared to the fixed speed wind turbine, which has popularised its application in power systems. Due to partial rated back-to-back converters in the doubly-fed induction generator, fault ride-through capability improvement is one of the important subjects in relation to new grid code requirements. To enhance the fault ride-through capability of the doubly-fed induction generator, many studies have been carried out. Fault current limiting devices are one of the techniques utilised to limit the current level and protect the switches, of the back-to-back converter, from over-current damage. In this paper, a review is carried out based on the fault current limiting characteristic of fault current limiting devices, utilised in the doubly-fed induction generator. Accordingly, fault current limiters and series dynamic braking resistors are mainly considered. Operation of all configurations, including their advantages and disadvantages, is explained. Impedance type and the location of the fault current limiting devices are two important factors, which significantly affect the behaviour of the doubly-fed induction generator in the fault condition. These two factors are studied by way of simulation, basically, and their effects on the key parameters of the doubly-fed induction generator are investigated. Finally, future works, in respect to the application of the fault current limiter for the improvement of the fault ride-through of the doubly-fed induction generator, have also been discussed in the conclusion section.

Highlights

  • With the high penetration level of wind energy conversion systems in the grid, power system operators encounter new challenging issues, which could affect the stability of the power system.keeping the wind turbines connected to the grid during faults with high wind power penetration is important, which is known as fault ride-through (FRT) capability [1].Due to many significant characteristics of doubly-fed induction generator (DFIG) based wind turbines, they are widely employed in the power system, especially for the multi-megawatt applications [2]

  • Keeping the wind turbines connected to the grid during faults with high wind power penetration is important, which is known as fault ride-through (FRT) capability [1]

  • From an impedance point of view, the Fault current limiters (FCLs) are mostly the resistive type, as it is clear from Figure 2

Read more

Summary

Introduction

With the high penetration level of wind energy conversion systems in the grid, power system operators encounter new challenging issues, which could affect the stability of the power system. Fault current limiters (FCLs) and series dynamic braking resistors (SDBRs) are placed in series connection, in different locations, in the. When adding new hardware into the DFIG, one of the common techniques is to employ fault current limiting devices to improve the FRT capability of the DFIG. Fault current limiters (FCLs) and series dynamic braking resistors (SDBRs) are placed in series connection, in different locations, in the DFIG (the stator side, the terminal, the DC link between the RSC and the DC-link capacitor, and the rotor side). The steady state of the fault condition is discussed, which essentially depends on the type and size of the impedance in the fault current limiting devices

Diagram
Section V
Doubly-Fed
Fault Ride-Through
Inductive
Fault Current Limiting Devices
Inductive Type FCL
Inductive-Resistive
Resistive Type FCL
Resistive
Resonance Type FCL
Series Dynamic Braking Resistor
Simulation Results
Conclusions