Abstract

High-frequency oscillation (HFO) is easy to occur in a flexible DC distribution system, due to the influence of the interaction of multiple time scale control links and physical circuits. This paper studies the mechanism of HFO and establishes a reduced-order mathematical model of a flexible DC distribution system based on droop control. Sensitivity analysis has been used to obtain a second-order system for mechanism analysis. The analytical equation of HFO is deduced in time domain considering the system parameters’ influence. This paper summarizes the influence law of the filter capacitor, equivalent inductance, and controller parameters on HFO. Finally, a simulation model of a low-voltage flexible DC distribution system is built based on Matlab/Simulink, and the simulation result verifies the validity of the theoretical analysis.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call