Abstract

Purpose Significant amount of harmonics and inter-harmonics are being injected into the power system because of the increasing use of power electronics and large non-liner loads. Therefore, analyzing their contents in real time is necessary. Design/methodology/approach The frequency and phase of an electric power harmonic or inter-harmonic can be estimated by using the discrete spectrum energy center of symmetric windows, the amplitude calculation of an electric power harmonic or inter-harmonic can be calculated by using the Pasival theorem, and their relative estimation error is only decided by the distribution of windows’ energy in the frequency domain, which equals the proportion of the spectrum energy occupied in the side lobe to the whole. Findings The results of the digital simulation and experimental tests show that the method proposed in this paper has the same measurement precision as and more advantages in computational complexity and burden over other methods, which are based on multipoint interpolation or interpolation polynomial windowed. Originality/value The method is very suitable to be used to real-time measurement in a single chip DSP micro-processor.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call