Abstract

AbstractThis paper presents a new solution method for computing the maximum loading point of a bulk power system under the condition where the loads of the nodes can be parameterized by a scalar which is the loading level of the system.A special loading model, in which the loading level of the system depends on the voltage magnitude of a loading node, is adopted for the purpose of releasing the load‐flow computation from the ill‐condition near and at the maximum loading point. The loading level of the system is unknown in the aforementioned loading model. The maximum loading point is obtained by adjusting the operating parameter so as to achieve the maximum loading.The operating parameter is adjusted in the converging process of the Newton‐Raphson iterative computation. The adjustment is computed based on the least squares estimation using the data set which is obtained from its own iteration process.It is shown in numerical examples that the proposed method is satisfactorily rapid, stable, and accurate.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.