Abstract

The natural draft dry cooling tower (NDDCT) is a critical facility for an indirect dry cooling power plant in arid area for its merit of excellent water-saving. While crosswind degrades the performance of a NDDCT by changing the flow field inside and outside. In order to quantitatively study the influence of different flow characteristics on the performance of a NDDCT, hence to grasp the affecting mechanism of crosswind, a half-cylindrical computational fluid dynamics (CFD) model of a Heller type 660 MW NDDCT is developed and validated by a hot state modelling test rig. A flow loss factor (FLF) is derived and verified to linearly describe the effect of local flow field changing on the overall performance of a NDDCT. Based on the conjoint studies of the local FLF variation trends and the changing processes of correspondent flow characteristics in each specific flow segments, the critical factors influencing the performance of a NDDCT are identified under different crosswind conditions.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.