Abstract
Depending on the capacity, type and location, distributed generation (DG) can have an impact on protection coordination of directional over-current relays for looped distribution systems. In this paper, a new index is proposed, “protection coordination index” (PCI), which can serve as an effective measure when planning the protection of meshed distribution systems with DG. A two-phase non-linear programming (NLP) optimization problem is proposed to determine the PCI by optimally calculating variations in the maximum DG penetration level with changes in the protection coordination time interval. Furthermore, the influence of connecting a DG at a certain location on the system PCIs is examined. The presented analysis is tested on the distribution section of the IEEE 14-bus and IEEE 30-bus systems. The PCI can serve as an efficient index for distribution system planners: (i) to determine the best DG candidate locations for utility owned DG and (ii) to evaluate the impact of a customer owned DG, considering distribution system protection.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.