Abstract

Cooling efficiency of a natural draft, dry cooling tower (NDDCT) is significantly affected under cross-wind condition and might decrease to 75 percent in the range of moderate to high wind-velocity condition. Separated flow occurring at the rear radiators, along with deflected plume exiting tower stack, reduces the cooling efficiency. Various researchers have recommended wind breakers to partially decrease the undesirable effect of the flow separation. But in the present research work, a new exit configuration has been proposed for tower stack, which could reduce the throttling effect of deflected plume. Numerical simulation of the proposed configuration showed improvement in the cooling efficiency up to 9 percent compared to the present, usual one at the generally investigated wind-velocity value of 10 m/s.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.