In this paper, a new and practical method is presented to investigate and improve the effect of distributed generation (DG) on recloser-fuse coordination. The main idea is to develop a comprehensive data base from fault currants and protection coordination status of electric distribution system (EDS) against different penetration/location of DGs. For large EDSs, this approach can be used for candidate buses only. The main consequence of this approach is getting a comprehensive perspective from sensitive of protection coordination to DG installation in each bus of EDS. Obtaining preference buses for DG installation and classification of appropriate methods for restoration of protection coordination are the other consequences of this study. The proposed method has been implemented on the IEEE 37-node test feeder as an unbalance EDS, by writing several scripts in MATLAB. The results show the economical and technical advantages of the proposed method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.