Abstract

Electrical earthing design surge protection relies on accurate determination of soil resistivity down the vertical soil profile. The study investigated soil resistivity of a rocky region in Ile-Ife, Nigeria, were wenner method claimed to be failed. Pole-pole and Schlumberger electrode configurations method were deployed and electrical resistivity (ER) methods involving both horizontal profiling (HP) and Vertical Electrical Resistivity (VES) using an intelligent machine – ABM 300 C. Measurements were made along seven traverses to revealed soil resistivity variation in the region. Forty-eight VES stations were occupied along the traverse using the Schlumberger array with electrodes spacing of (AB/2) varying from 1 to 60 m. The vertical electrical sounding data were interpreted quantitatively by partial curve matching and iterative modelling using WinglinkTM software. Geoelectric sections were generated on each of the traverses using the VES interpretation results. The result of this research revealed variation down the layers (profile). The resistivity ranges from 30 Ohms-m to 4893 Ohms-m and the thickness from 0.44 m to 13.7 m within the conductive layers respectively.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.