Abstract

A 126kV circuit breaker was found to have latent fault by SF6 decomposition product detection method. It was found that the sulfur hexafluoride gas decomposition products of the circuit breaker contained a large amount of CO gas, a certain amount of SO2 and H2S, and a small amount of HF gas. The characteristic components and their contents of the decomposition products were analyzed, it is preliminarily concluded that there is insulation material fault in the circuit breaker, and the potential fault is further confirmed by the disassembly inspection that the MoS2 lithium base grease is overcoated at the metal tie rod joint.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.