Abstract

To overcome shortages in the traditional current differential protection for HVDC transmission lines, a pilot protection based on transient energy ratio is proposed. The fault identification criterion is put forward based on the impedance-frequency characteristic of the line boundary, and the fault analysis which shows that under internal faults, with regard to either terminal of the dc line, the transient energy within a specific frequency band on the line side of the boundary is much greater than that on the valve side of the boundary, whereas after rectifier-terminal (inverter-terminal) external faults, the transient energy on the line side of the rectifier-terminal (inverter-terminal) boundary is much less than that on the valve side of the boundary. Moreover, the lightning disturbance identification criterion is implemented based on the magnitude ratio of fault components of high- and low-frequency band currents. Fault-pole selection is constructed by using the fault components of pole voltages. Simulation results demonstrate that the proposed scheme, with low computational complexity, can distinguish internal faults from external ones and protect the entire line reliably. It can also identify high-impedance faults and select the faulted pole correctly. Besides, it is not subject to lightning interferences and the dc line distributed capacitor.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.