Abstract

A partial discharge (PD) detection method for SF6 insulated inverted current transformers (SIICTs) adopting an inner shield case as an ultra-high frequency (UHF) sensor is proposed in this paper. The inner shield case is a component of the SIICT. Its structure is similar to that of an antenna and can be used as a UHF sensor to measure the PD UHF signal. A 110 kV current transformer is used as an experimental object and the voltage standing-wave ratio of the inner shield case is calculated. The validity and sensitivity of this method are proved by experiments with ac voltage. This PD detection method solves the problem that the UHF sensor is difficult to mount inside current transformers and provides a novel method for PD detection of SIICTs.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.