Abstract

The evaluation of the available safe egress time (ASET) is essential for organizing people evacuation in case of fire in buildings or generic enclosures. Especially, the evacuation on the building structure equipped the sprinkler systems are essential nowadays because sprinkler systems are widely used and impact directly on the fire characteristics. Therefore, we performed a numerical study for finding out the effect of sprinkler systems on the ASET by Fire dynamic simulators (FDS). In this article, we conducted a numerical study of fire in a cinema equipped with automatic sprinkler systems. The fire was made from a chair and spreading rapidly to the others in the cinema. The study tested various sprinkler pressure: 0.5 bar, 1 bar, and 1.3 bar and different fire locations. ASET was considered life safety criteria based on Korea regulation: temperature and visibility. As a result, ASET estimated at least 120s and effected slightly by the pressure of sprinkler.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.