Abstract

Phase change thermal energy storage (PCTES) technology has garnered significant attention in addressing thermal management challenges in building HVAC systems. However, the cooling performance of PCTES systems in humid scenarios remains unexplored, which is crucial in subtropical regions, high-humidity underground areas, and densely populated spaces. Taking the mine refuge chamber (MRC) as an example, this study focuses on a passive temperature and humidity control system by employing cold storage phase change plates (PCPs) for 96 h. First, an improved and simplified full-scale numerical model including PCPs and MRC parts is established. Then, the model is validated through the experimental results and solved using a numerical method. Finally, the influence of various factors within the system is investigated and an optimization method involving batch operation is proposed. The results indicate that (1) within 40 h, the use of cold storage PCPs leads to an indoor temperature reduction of 4.8 °C and a 7% decrease in relative humidity; (2) the PCPs show asynchronous states in sensible and latent heat transfer rates; (3) for every 50 additional PCPs, the average indoor temperature increases by 0.6 °C and the relative humidity decreases by 1.5%; (4) implementing batch operation of PCPs ensures that the indoor Heat Index drops by 10 °C, which is vital for human survival. The findings will play a crucial role in the global expansion and application (including geographical and functional aspects) of phase change thermal storage technology.