Abstract

This paper deals with the use of a continuous wavelet transform (CWT) to distinguish faults in a busbar protection zone from those outside the zone. The Morlet wavelets are used as the wavelet basis function. They are more efficient in monitoring fault signals as time varies. The differential current as the operating quantity and the sum of the current magnitudes as the stabilizing signal are computed. The magnitudes of the CWT of these currents are derived to obtain the operational and restraint signals. The CWT coefficient plots are given to precisely determine the scale of analysis. The proposed wavelet transform approach based on Morlet basis function is found to be an excellent discriminant for identifying the fault signals during the CT saturation and ratio mismatch. ATP simulations are used to test and validate the proposed CWT approach for model power system faults.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.