Abstract
In this paper, a new voltage sag approach is analytically modelled and validated using both simulation and field measurements. The main aspect of this approach is to propose a new voltage sag feature which appears during unintentional islanding operations (IOs). The unintentional IO occurs when an induction motor is removed from the main utility following a circuit breaker (CB) clearing, transiently, the induction motors (IMs) are acting as generators maintaining the affected distribution feeder with voltage until it is reconnected. The voltage sag modelled in the current article follows an exponential form, as a matter of fact, here it will be demonstrated that the proposed model reaches satisfactorily the field measurements and evidences the dependability of the model adopted. Furthermore, it is worthwhile to note that this novel power quality (PQ) event has not been investigated yet and enhances voltage sag studies. Lastly, it is crucial to point out that all recorded events and a large amount of data needed so as to validate this transient, has been measured in a distribution network (DN) located in Spain.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.