Abstract

A novel unit transient based protection criterion for high voltage power transmission line based on the wavelet transform results of voltage transient signals at each end of the line is presented. The transient voltage content ratio (TVCR) and transient voltage singularity ratio (TVSR) are deduced according to the difference of high frequency voltage transients at each end of the transmission line when in-zone faulted and out-zone faulted. Protection criterion using TVSR is proposed, and the principles of protection settings are given. The criterion is suitable for both two-end line and T-type line. Simulations of different faults and different line types are carried out for testing and analyzing the protection criterion.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.