Abstract

The accurate measurement of the ground capacitance is helpful to ensure the compensation effect of the arc suppression coil. To improve the accuracy of measurement, a unified measurement method for ground capacitance and arc suppression coil inductance based on signal injection method and fast Fourier transform (FFT) is proposed. Firstly, the relationship between the neutral voltage and the system parameters is established. Secondly, current at a specific frequency is injected into the neutral point, and the neutral voltage component at the specific frequency is obtained by FFT to eliminate the power frequency error. Then the unified measurement is realized according to the equivalent circuit. Finally, the proposed method is tested by the MATLAB/Simulink, which shows that this method is suitable for various types of arc suppression coils. In the three-phase asymmetry condition, the maximum errors of ground capacitance and arc suppression coil inductance are 0.1% and 0.11% respectively, and the maximum errors are 1.3% and 1.8% respectively in three-phase symmetry condition.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.