Abstract

A novel transmission-line monitoring method for estimating the transient voltage from the transient current alone is presented. This is based on the properties of traveling waves instigated on high-voltage transmission lines as a result of a fault, switching operation, or a lightning strike. The method is unique in that superimposed voltage transients can be deduced without employing measurements taken from voltage transducers. It is demonstrated that full advantage can be made of the broad bandwidth of the current transducers to improve fault location and enable high-speed traveling wave protection to be applied on power systems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.