Abstract

Background:: The large-scale aging of cross-linked polyethylene (XPLE) leads to an increase in the frequency of power cable accidents, which poses a threat to the safe operation of the power grid. Objective:: Traditional time-frequency domain reflectometry (TFDR) techniques for fault localization in power cables are susceptible to cross-terms interference, which makes it impossible to accurately locate defects. To overcome the limitation, this paper has proposed a novel cable fault localization method based on S-transform. Method:: The method employs S-transform to perform time-frequency analysis on the collected signals of TFDR, mapping the time-domain signals into time-frequency domain signals. Then, cross-correlation of the time-frequency domain signals is estimated, allowing for accurate positioning of cable defects. Results:: The results of the field experiments conducted on a 10 kV cross-linked polyethylene cable with artificially introduced defects have demonstrated that the proposed method could effectively locate the cable defects with small absolute error. Conclusion:: Compared to existing TFDR methods, the proposed method has been found to be free from interference of cross-terms, resulting in higher reliability and smaller blind spots for detecting cable defects.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call