Abstract

For the insulation diagnosis of GIS, it is necessary to detect partial discharge (PD) under noisy condition and to specify the direction of electromagnetic wave radiation due to PD. We proposed "phase gate control method" for discriminating the electromagnetic wave caused by PD in SF/sub 6/ gas from external noises. The proposed method enabled us to discriminate PD of about 100 pC in SF/sub 6/ gas from external noises of more than 10000 pC in air. We also compared polarization characteristics of electromagnetic wave radiated from PD with those from a half-wave dipole antenna, and could estimate the radiation length of electromagnetic wave caused by PD. The results derived in this paper contribute to the insulation diagnosis of GIS on-site.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.