Abstract

This paper presents a new fault detection and diagnosis (FDD) strategy for centrifugal chillers in building air-conditioning systems. The strategy is implemented using the fuzzy modeling and the artificial neural network techniques. Based on the sensitivity analysis of performance indices (PIs) to the chiller faults, the PI residuals between the model estimations using the normal data and the model estimations using the fault data are chosen to be normalized and to form a diagnostic classifier. The chosen PI risiduals are further quantified by the proposed fuzzy models. The fault identification is realized by neurasl network, using the quantitative diagnostic classifier. The use of the quantitative diagnostic classifier in this FDD strategy overcomes the problem faced by classical qualitative fault classifiers when different faults have the same linguistic rule pattern. The strategy implementation is based on the data at normal and faulty operating conditions at a range of load levels and fault severity levels. The strategy is validated using the laboratory chiller data provided by ASHRAE Research Project RP-1043 (Comstock and Braun 1999c).

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.