Abstract

AbstractAn effective system control method is presented for applying a three‐phase current‐source PWM converter with a deadbeat controller to active power filters (APFs). In the shunt‐type configuration, the APF is controlled such that the current drawn by the APF from the utility is equal to the current harmonics and reactive current required for the load. To attain the time‐optimal response of the APF supply current, a two‐dimensional deadbeat control scheme is applied to APF current control. Furthermore, in order to cancel both the delay in the two‐dimensional deadbeat control scheme and the delay in DSP control strategy, an Adaptive Line Enhancer (ALE) is introduced in order to predict the desired value three sampling periods ahead. ALE has another function of bringing robustness to the deadbeat control system. Due to the ALE, settling time is made short in a transient state. On the other hand, total harmonic distortion (THD) of source currents can be minimized compared to the case where ideal identification of the controlled system can be made. The experimental results obtained from the DSP‐based APF are also reported. The compensating ability of this APF is very high in accuracy and responsiveness although the modulation frequency is rather low. © 2004 Wiley Periodicals, Inc. Electr Eng Jpn, 150(1): 50–61, 2005; Published online in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/eej.20014

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.