Abstract
Commutation failure (CF) threatens system safety with traditional HVDCs. To improve the recovery performance from CF, a novel recovery strategy is proposed, where a dynamic current ramp limiter is introduced to reduce the probability of current overshot during the recovery. The dynamic ramp limiter is designed based on the idea of judging the system recovery state by the dc current level, where a high level corresponds to a high risk of CF. The ramp limit is calculated by the frequency constraint of ac systems. Case studies based on a real-world system are used to verify the effectiveness of the proposed method, and the results show that the proposed method can improve the recovery performance and avoid the continuous CFs.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.