Abstract

A new fault location principle using one terminal voltage and current data for EHV transmission lines is described in this paper, which is based on distributed parameter line model, breaking through the traditional single-ended fault location ideas. The voltage along the healthy line could be calculated using single-ended voltage and current data; however, the voltage behind the fault point is not true for a faulted line. Even though, notice the fact that the norm value of derivative function of the fictitious profile to distance is minimum at fault point, based on which the fault location function is constructed. The numerical algorithm is also described; this principle is proved by EMTP simulations to be immune to fault resistance, fault types, and fault inception angle. Theoretically, the accuracy of the principle is proportional to the sampling rate of the locator.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.