Abstract

This paper presents a version of the Newton-Raphson (NR) algorithm that has been modified to provide a means of facilitating the power flow analysis of loop systems in the presence of current sources that rely on current controlled inverters, such as distributed generators (DGs). The modifications entail the inclusion of the current elements of current sources in the Jacobian matrix of the NR algorithm. The effect is to enable current controlled sources to be modeled directly in the power flow algorithms without the need for converting their currents to the corresponding power components, which is the traditional practice in power flow algorithms. The proposed algorithm has been tested on an IEEE 14-bus system. For loop systems with current controlled sources, the test results show that using this algorithm for power flow analysis offers enhanced accuracy.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.