Abstract

In this paper, a novel method based on waveform longitudinal symmetry coefficient is proposed to identify the inrush current and fault current for transformer protection. Because the fault current waveform has characteristic of approximate symmetry, its longitudinal symmetry coefficient is nearly zero and less than 0.10. But the inrush current waveform is longitudinal asymmetrical, and its longitudinal symmetry coefficient is larger and more than 0.15 in normal conditions. The result of simulation demonstrated the method is valid and less affected by CT saturation and high harmonics.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.