This paper presents a novel method for the removal of dual decaying DC offsets (DDCOs) to enhance discrete Fourier transform-based phasor estimation. The method proposed in this paper uses the sum of even samples and the sum of odd samples from the input signal to remove the AC components, thereby precisely estimating the primary and secondary DDCOs. The fluctuations induced by DCCOs present in the output of traditional DFT methods are eliminated by using the estimated DCCOs. The performance of the method was evaluated in terms of both mathematical-generated signals and fault current signals from a 154 kV Korean overhead transmission system. PSCAD/EMTDC was used to generate fault current signals at various fault distances and angles. The results show that the proposed method can estimate the phasor of the fundamental frequency component accurately regardless of the primary and secondary DCCOs. The paper concludes by describing the hardware implementation in a prototype unit that considers the real-world requirements of power system protection.