Abstract

Large disturbances in power systems cause deviation in the frequency from the nominal value. Since the frequency is an important factor in the electrical network parameter measurements, it can cause malfunction of the protection system. In addition, Because of decaying DC and oscillatory components that introduced by CCVT in response of voltage variation during the fault occurrence, cause changes in the value of received voltage of primary side of CCVT. An improved least square method for estimating frequency is presented in this paper. In order to reduce the effect of this transient component, phasor estimation method has been improved by using the least square technique and utilizing knowledge of CCVT design. The capability of the proposed method was verified by several case studies generating signals in PSCAD/EMTDC. The results show the accuracy, speed and capability of the proposed method

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.