Abstract

Leakage current measurement is the most reliable and effective method for condition monitoring of overhead insulators deployed in the field. However, a major challenge in the leakage current based insulator monitoring is to interpret the indices extracted from the leakage current measurements under varying harmonic content in system voltage. This paper reports the possibility of employing the instantaneous value of time-integral of leakage current as a low-sensitive parameter for the monitoring of leakage current in overhead insulators in the presence of voltage harmonics. It has been shown that any change in the harmonic content of the system voltage has a significant influence on the harmonic characteristics of the leakage current, but has a comparatively less severe effect on the time-integral. The monitoring technique has been validated through laboratory recorded experimental data and incorporated in an online measurement device that has been tested in the laboratory.