Abstract
This paper presents a new scheme to distinguish the internal fault or the external fault based on phaselet algorithm. For the generator ratio restraint differential protection, the restraint current is decreased owing to CT saturation caused by the external fault, which always results in the maloperation. In order to enhance the operating characteristic of the protection, generator differential protection will select different restraint currents according to the different fault current characteristics. According to that, the method for choosing the corresponding restraint currents is then introduced. The simulation results show that the scheme can effectively prevent the generator differential protection from maloperation caused by CT saturation, and availably enhance the sensitivity of the differential protection during the internal fault.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.