Abstract

<para xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"> A circuit configuration of a single-phase nonisolated online uninterruptible power supply (UPS) with 110-V/220-V input–output voltage ratings is proposed, allowing the bypass operation without a transformer even if the input voltage is different from the output voltage. The converter consists of an ac–dc/dc–dc three-level boost converter combined with a double half-bridge inverter. In this type of configuration size, cost and efficiency are improved due to the reduced number of switches and batteries, and also, no low-frequency isolation transformer is required to realize bypass operation because of the common neutral connection. Both stages of the proposed circuit operate at high frequency by using a passive nondissipative snubber circuit in the boost converter and insulated-gate bipolar-transistor switches in the double half-bridge inverter, with low conduction losses, low tail current, and low switching losses. Principle of operation and experimental results for a 2.6-kVA prototype are presented to demonstrate the UPS performance. </para>

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.