Abstract
The winding impedance spectrum method becomes popular in online stator insulation monitoring in recent years. It can detect the insulation ageing condition and give alarm before catastrophic failure happens. However, the theoretical explanation of this method is not sufficient and the relationship between impedance spectrum and insulation ageing is not clear. In addition, the existing methods need additional signal injection equipment, which is intrusive and difficult to be applied in industrial applications. Therefore, this article develops a noninvasive interturn insulation condition monitoring method based on the common-mode impedance spectrum in inverter-fed machines. By building a broadband stator winding insulation model, the relationship between the interturn insulation ageing and the impedance spectrum is studied and the high frequency parallel capacitance is first proposed as an indicator for the interturn ageing. The offline test validate the effectiveness of the proposed method and the online test shows the potential of this method for noninvasive condition monitoring in inverter-fed machines. Future work is planned to further improve the online performance of the proposed method.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.