Abstract
In islanded microgrids, distributed generators (DGs) are employed as distributed compensators to improve the power quality on the load side. Due to the access of unbalanced loads, the low-voltage microgrid will naturally exhibit three-phase unbalance, which may cause additional power losses and deteriorate power quality. Therefore, this paper proposes a novel unbalanced-voltage compensation control method based on the Hopf oscillator, which introduces the negative-sequence voltage and current into the traditional Hopf oscillator to achieve the negative sequence voltage droop characteristics. It can not only realize the negative sequence droop control of a single inverter, but it is also capable to support the reactive power automatic distribution between multi-parallel grid-forming inverters. Compared with the traditional unbalanced voltage compensation method based on filtered negative sequence reactive power, the proposed unbalanced voltage compensation method can slightly improve the dynamic response. Experimental results verify the effectiveness of the proposed control strategy.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.