Abstract

To ensure safe re-energizing of an overhead distribution feeder after it is de-energized for an extended period, a novel fault detection technique by controlling a thyristor-based device is proposed in a companion paper. The device connected in parallel with a breaker or recloser can inject electrical pulses with adjustable strength for the downstream fault detection in a de-energized system. The proposed method can effectively detect different kinds of asymmetrical faults based on the unbalanced fault currents. However, the unbalanced current-based fault detection scheme is not effective for three-phase symmetrical faults detection. Furthermore, a stalled motor or a shunt-connected capacitor bank in the downstream may also behaves like a short-circuit. Therefore, a fault detection algorithm based on the analysis of the harmonic impedance of the de-energized system is developed in this paper. This method is very effective for the symmetrical fault detection and for distinguishing a stalled motor and capacitor bank from a fault. Extensive lab test results are provided in the paper to verify the effectiveness of the proposed method.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.