Abstract
This paper proposes the application of moving window averaging technique for differential protection of transformer. The instantaneous currents of primary and secondary are transformed by using moving window averaging technique for the window width of one cycle. The steady state values of transformed currents are zero for a sinusoidal signal. However, the presence of harmonic and dc offset may deviate it from its nominal zero value. The energization of transformer leads to decaying transient inrush current which mal-operate the differential relay. The power transformer is modeled in ATP-EMTP environment considering core nonlinearities and losses so as to capture inrush current. The moving window averaging technique based current differential protection algorithm is implemented in MATLAB. The relay is tested for various internal and external faults. The result promises applicability of proposed algorithm for protection of transformer.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.