Abstract

A new protective meausre installed in the grid connected dispersed PV system for detecting short circuit fault with high-resistance in a high-voltage distribution line was designed. Relationship between voltage absolute value change and voltage phase change of the distribution line is monitored in the measure for achieving not only enhancement of detective performance but also prevention of misdetection in normal operation of the grid. It was clear from simulation results that the number of PV systems detecting the fault increased about 2 times as much as the existing method and the reduction of fault current at utility substation, which causes dangerous inability of utility's protection, could be prevented effectively.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.