Abstract

This paper presents a new adaptive fault protection scheme for transmission lines using synchronized phasor measurements. The work includes fault detection, direction discrimination, classification, and location. Both fault-detection and fault-location indices are derived by using two-terminal synchronized measurements incorporated with distributed line model and modal transformation theory. The fault-detection index is composed of two complex phasors and the angle difference between the two phasors determines whether the fault is internal or external to the protected zone. The fault types can be classified by the modal fault-detection index. The proposed scheme also combines online parameter estimation to ensure protection scheme performance and achieve adaptive protection. Extensive simulation studies show that the proposed scheme provides a fast relay response and high accuracy in fault location under various system and fault conditions. The proposed method responds very well with regards to dependability, security, and sensitivity (high-resistance fault coverage).

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.