Abstract

A new non-unit voltage protection algorithm for extra high voltage (EHV) transmission lines is presented in this paper. The singularity of fault transient voltage signals in one terminal is utilized to discriminate clearly between internal and external faults. Lipschitz exponent (LE) is obtained from wavelet modulus maximum to detect singularity of signals. A typical 500 kV EHV transmission system has been simulated by ATP to evaluate the scheme. The simulation results show that this scheme is capable of providing correct responses under various system configurations and fault conditions

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.