Abstract

The fact of a dominant resonance frequency existed in the transient process of short-circuit fault is discovered by analyzing transient characteristics of singlephase earthed fault. At this frequency, the magnitude of zero modal current in faulty feeder is much larger than that in healthy feeder, and their phase is approximately opposite. Dominant transient frequency(DTF) zero modal current in faulty feeder is 90° lagging behind zero modal voltage of bus bar, while for healthy feeder it is 90° leading zero modal voltage of bus bar. A novel detection principle based on Prony algorithm is presented in the paper, which determines the faulty feeder by comparing the magnitude of DTF current of faulty feeder and healthy feeder. It is verified by ATP simulation data and field measured fault data respectively.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.