Abstract

In this letter a new power-based digital algorithm is introduced to provide protection for the generators against unbalanced faults. The algorithm measures the generator's three-phase power output and monitors the sinusoidal component of the instantaneous power. When the magnitude of the sinusoidal component exceeds a predefined value, the algorithm checks the direction of the negative sequence-reactive power flow to discriminate between internal and external faults. The proposed algorithm initiates fast tripping for internal asymmetrical faults, and provides back up protection for external unbalanced conditions.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.