Abstract

In conventional transmission line protection, a distance relay is used to provide the primary as well as remote backup protection. The voltage and current phasors measurement needed by the distance relay for determining the impedance may be affected by the power disturbances such as power swing. Consequently, this power swing may cause mal-operation of Zone three distance relays which in turn may affect on the reliability of the whole protective scheme. To mitigate these effects and hence improve the relay reliability, this work proposes a new real-time power swing detector using phasor measurement units for blinding the distance relay only during this transient disturbance. However, this developed detector will not block relay when the power swing accompanied with faults. To validate the present work, the performance of developed enhanced distance relay is tested by signals generated by Simulink/MATLAB simulator under different conditions. The test results show that this proposed scheme provides good discrimination between the transient currents and the fault current which in turn it may contribute in enhancing the reliability of Distance relay.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.