The amount of power flowing through a high-voltage transmission line is proportional to its voltage and the current flowing through it. To increase power flow without modifying the line to allow increased voltage, the current must be increased. There is a limit to this, however, since increasing the current causes the conductor temperature to increase and hence the conductors to elongate and sag. In this paper, a method to simply and inexpensively measure the amount of conductor sag and, by simple calculation, the average conductor core temperature is described and the results of a field test are summarized. The method involves attaching two ends of a grounded wire of high electrical resistance to an appropriate location on each of two transmission line towers and measuring the current induced on the wire by the nearby transmission line conductors. Information from this measurement is a critical input to any method for dynamically rating transmission lines.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.