Abstract

It is difficult to select the fault line due to the weak current when the single-phase grounding fault occurs in the resonant grounding system. A new method based on correlation between zero-sequence voltage in bus and zero-sequence current in feeders is proposed in this paper. The correlation coefficient is less than zero because the polarity of zero-sequence voltage and zero-sequence current is opposite in fault line, and correlation coefficient is large than zero because the polarity in sound line is same. Therefore, the feeder what corresponding to the minimum correlation coefficient is the fault line. Most simulation results show that in resonant grounding system, compared with the integrated correlation coefficient analysis between pure fault components of zero-sequence current from every line, this method can be applied to select fault line more better, and misjudgment will not be caused.1

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.