Abstract

In this paper, a new method is proposed for discriminating internal faults from other abnormal conditions in power transformers such as inrush currents, external faults, over-excitation, and ultra-saturation. Since the differential current signals are non-stationary, a powerful tool such as S-transform is needed for their time-frequency analysis. In this study, some important characteristics are extracted using the Clark’s transform and modified hyperbolic S-transform according to which different conditions are distinguished and classified. These features include energy contour of first level, variance index, standard deviation of second harmonic component, and a special criterion. In this paper, all possible transient conditions and the effects of the saturation of current transformers are considered. Various simulations for different operating conditions of transformer are performed via PSCAD/EMTDC software. Also, the entire process of modified hyperbolic S-transform and the proposed algorithm are done in MATLAB software. Simulation results show that the proposed algorithm can be reliably used for the identification and classification of different faults in transformers.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.