Abstract
This paper presents a technique that increases the second-zone coverage of distance relays without causing overreach problems. The technique is based on the impedance seen by distance relays when faults are simulated on the reach of zone-1 relays. The approach checks the relay operation for the maximum as well as the minimum generation outputs of the power system. Simulations of different operating conditions of a power system in different configurations were used to test the approach. The proposed technique can be used for different reach setting for zone-1. Results show that it is possible to increase the coverage provided by zone-2 distance relays without causing coordination problems with the primary relays that protect the lines emanating from the remote bus.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.