Abstract
With the advent of Substation Computer Systems dedicated to protection, control and data logging functions in a Substation, it becomes possible to develop new applications which can utilize the processing power available within the substation. The microcomputer based Symmetrical Component Distance Relay (SCDR) described in the references cited at the end of this paper possesses certain characteristics which facilitate real-time monitoring of positive sequence voltage phasor at the local power system bus. With a regression analysis the frequency and rate-of-change of frequency at the bus can also be determined from the positive sequence voltage phase angle. This paper describes the theoretical basis of these computations and describes results of experiments performed in the AEP power system simulation laboratory. Plans for future field tests on the AEP system are also outlined.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.