Abstract
<para xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"> For a grid-connected converter with an LCL filter, the harmonic compensators of a proportional–resonant (PR) controller are usually limited to several low-order current harmonics due to system instability when the compensated frequency is out of the bandwidth of the system control loop. In this paper, a new current feedback method for PR current control is proposed. The weighted average value of the currents flowing through the two inductors of the LCL filter is used as the feedback to the current PR regulator. Consequently, the control system with the LCL filter is degraded from a third-order function to a first-order one. A large proportional control-loop gain can be chosen to obtain a wide control-loop bandwidth, and the system can be optimized easily for minimum current harmonic distortions, as well as system stability. The inverter system with the proposed controller is investigated and compared with those using traditional control methods. Experimental results on a 5-kW fuel-cell inverter are provided, and the new current control strategy has been verified. </para>
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.